Recommended Spacing

Recommended Spacing
Pipe or Tube OD Operating
Pressure
Recommended
Spacing
Operating
Pressure
Recommended
Spacing
0.250 in. to 0.675 in. up to 3000 psi 5-7 Ft. over 3000 psi 3-5 Ft.
0.750 in. to 1.050 in. up to 3000 psi 6-8 Ft. over 3000 psi 4-6 Ft.
1.125 in. to 1.500 in. up to 3000 psi 7-9 Ft. over 3000 psi 5-7 Ft.
1.750 in. to 2.500 in. up to 3000 psi 8-10 Ft. over 3000 psi 6-8 Ft.
2.750 in. to 3.500 in. up to 3000 psi 9-11 Ft. over 3000 psi 7-9 Ft.
4.000 in. to 4.500 in. up to 3000 psi 10-12 Ft. over 3000 psi 8-10 Ft.
5.563 in. to 6.625 in. up to 3000 psi 11-13 Ft. over 3000 psi 8-11 Ft.
6.625 in. to 8.625 in. up to 3000 psi 12-14 Ft. over 3000 psi 9-11 Ft.
10.750 in. to 12.750 in. up to 3000 psi 13-15 Ft. over 3000 psi 8-10 Ft.
13.750 in. to 19.750 in. up to 3000 psi 14-16 Ft. over 3000 psi 10-12 Ft.
Recommended Mounting Practices
Bends
Behringer recommends that all pipe bends be supported by clamps placed as close to the bend as possible. The clamps should be directly after the connection (coupler, threaded connector, flange, orother).

  
Components
Behringer recommends that all system components are supported by a clamp directly before and after the component in order to protect against vibrations and shock. Clamps should be located as close to the component as possible.